Skip to content
3FOLD Training
  • Home
  • About Us
  • Courses
    • AACE
      • Certified Cost Professional
    • ASQ
      • Certified Manager of Quality
      • Certified Six Sigma Green Belt
      • Certified Six Sigma Black Belt
    • CQI IRCA
      • ISO 9001:2026 QMS Lead Auditor
      • ISO 14001:2026 EMS Lead Auditor
      • ISO 27001:2022 ISMS Lead Auditor
      • ISO 45001:2018 OHSMS Lead Auditor
    • GBCI
      • LEED Green Associate
      • LEED Accredited Professional
      • LEED GA & AP (BD+C) Combo
    • PMI
      • Project Management Professional
    • Transition
      • ISO 9001:2026 Transition
      • ISO 14001:2026 Transition
  • Schedules
  • Articles
  • Testimonials
  • Webinars
  • Contact us
Community Join 3FOLD Training Schedules on WhatsApp — get every course batch update first 3FOLD Training Schedules on WhatsApp Join now

UAE +971 50 481 9989 | India +91 91762 57536

online@3foldtraining.com
3FOLD Training3FOLD Training
  • Home
  • About Us
  • Courses
    • AACE
      • Certified Cost Professional
    • ASQ
      • Certified Manager of Quality
      • Certified Six Sigma Green Belt
      • Certified Six Sigma Black Belt
    • CQI IRCA
      • ISO 9001:2026 QMS Lead Auditor
      • ISO 14001:2026 EMS Lead Auditor
      • ISO 27001:2022 ISMS Lead Auditor
      • ISO 45001:2018 OHSMS Lead Auditor
    • GBCI
      • LEED Green Associate
      • LEED Accredited Professional
      • LEED GA & AP (BD+C) Combo
    • PMI
      • Project Management Professional
    • Transition
      • ISO 9001:2026 Transition
      • ISO 14001:2026 Transition
  • Schedules
  • Articles
  • Testimonials
  • Webinars
  • Contact us

Auditing Annex A.7: Physical Controls

November 13, 2026 Posted by 3FOLD ISO 27001, Lead Auditor No comments

PR373 · ISO/IEC 27001:2022 ISMS Lead Auditor12 min read

Annex A.7 Physical Controls: What an Auditor Tests

A.7 has fourteen controls covering perimeters, entry, secure areas, environmental threats, equipment and disposal. It is the one theme where the strongest evidence is something you can see, and the theme most often audited badly — by walking a building and admiring the locks rather than testing what the organisation said it would do.

3FOLD TRAINING · CQI and IRCA Approved Training Partner (ATP 6039853) · Course Approval No. 2889
14
Controls in A.7
1
New in 2022: A.7.4
2
Worked findings from one visit

In this guide

  • The fourteen ISO 27001 Annex A.7 physical controls, by control number
  • What an ISO 27001 physical controls audit is actually testing
  • Where ISO 27001 Annex A.7 is usually strong, and where it is usually thin
  • Two worked ISO 27001 findings on Annex A.7, from one visit
  • Observation in an ISO 27001 audit, and its limits
  • Major or minor in ISO 27001 Annex A.7
  • The other three ISO 27001 Annex A themes

A.7 has fourteen controls covering perimeters, entry, secure areas, environmental threats, equipment and disposal. It is the one theme where the strongest evidence is something you can see, and the theme most often audited badly — by walking a building and admiring the locks rather than testing what the organisation said it would do.

The organisation in the worked findings on this page is invented, and so are the findings.

The fourteen ISO 27001 Annex A.7 physical controls, by control number

ControlIn one line
A.7.1 Physical security perimetersPerimeters defined and used to protect areas containing information and other associated assets
A.7.2 Physical entrySecure areas protected by appropriate entry controls and access points
A.7.3 Securing offices, rooms and facilitiesPhysical security for offices, rooms and facilities designed and implemented
A.7.4 Physical security monitoringPremises continuously monitored for unauthorised physical access — one of the eleven controls the 2022 revision added
A.7.5 Protecting against physical and environmental threatsProtection against physical and environmental threats, such as natural disasters and other intentional or unintentional threats, designed and implemented
A.7.6 Working in secure areasSecurity measures for working in secure areas designed and implemented
A.7.7 Clear desk and clear screenClear desk rules for papers and removable storage media, and clear screen rules for information processing facilities, defined and appropriately enforced
A.7.8 Equipment siting and protectionEquipment sited securely and protected
A.7.9 Security of assets off-premisesOff-site assets protected
A.7.10 Storage mediaStorage media managed through their life cycle of acquisition, use, transportation and disposal, in accordance with the classification scheme and handling requirements
A.7.11 Supporting utilitiesInformation processing facilities protected from power failures and other disruptions caused by failures in supporting utilities
A.7.12 Cabling securityCables carrying power, data or supporting information services protected from interception, interference or damage
A.7.13 Equipment maintenanceEquipment maintained correctly to ensure availability, integrity and confidentiality of information
A.7.14 Secure disposal or re-use of equipmentItems of equipment containing storage media verified to ensure that any sensitive data and licensed software has been removed or securely overwritten prior to disposal or re-use

Remember where the control came from. Annex A is a reference set, and a control is on the audit’s agenda because the organisation selected it at Clause 6.1.3 and recorded that in the Statement of Applicability. What that document claims is the first thing to test. It is worth doing here in particular: physical arrangements are inherited, and an organisation frequently has protection it never selected and never wrote down.

Looking for an approved provider?3FOLD TRAINING is a CQI and IRCA Approved Training Partner, ATP 6039853.

Check the next batch

What an ISO 27001 physical controls audit is actually testing

Not whether the building is secure. Whether the arrangements the organisation determined it needed are the ones in place. A building with card readers, cameras and a manned reception can fail A.7 comfortably, if what its own policy says about secure areas is not what the secure areas do. And a modest office with two locked rooms can pass, if the two rooms are the ones its risk assessment identified and the arrangements match.

That has a practical consequence for the order of work. Read before you walk. The site plan, the definition of secure areas, the entry rules, the maintenance schedule and the disposal arrangements are all documents, and they become your criteria. Walking first produces observations you have nothing to measure against, and an auditor with observations and no criteria writes opinions.

Where ISO 27001 Annex A.7 is usually strong, and where it is usually thin

Physical security is the oldest discipline in the annex, and most organisations have inherited arrangements that work. The perimeter, the entry system and the server room are normally in reasonable order, and a great deal of audit time gets spent confirming it.

The thin ground is elsewhere, in four controls that rarely get attention.

A.7.11 supporting utilities. An uninterruptible power supply and a generator are common; records that either has been tested under load are not. The control asks for protection from failures in supporting utilities, and untested protection is an assumption.

A.7.13 equipment maintenance. Maintenance is normally somebody else’s schedule — facilities, or a contractor. The information security question is whether it happens as specified, and what the engineer has access to while it does.

A.7.12 cabling security. Almost never examined, and the one control in the theme where a fifteen-second look at a comms room usually settles it.

A.7.9 security of assets off-premises. Written for laptops in an era before most of the workforce was off-premises most of the time. Read the organisation’s own arrangements and test them against how people actually work.

Preparing for the PR373 exam?Full-length mock exams and exam application support are included.

See what’s included

Two worked ISO 27001 findings on Annex A.7, from one visit

Wraysbury Castings operates two foundries and a head office, with a server room at head office protected by card entry and an environmental monitoring system.

The same afternoon in the facilities office produced two findings. They are set out separately because they are two requirements, resting on different evidence and needing different corrective action. Bundling them into one nonconformity would have given the organisation a single response to write and one of the two problems would have survived it.

The first: A.7.11

StatementTesting of the supporting utilities protecting the head office information processing facilities is not performed to the organisation’s own specification.
Objective evidenceThe physical security procedure requires the head office uninterruptible power supply to be load-tested every six months and the standby generator to be run under load every quarter, with results recorded in both cases. The generator log for the period shows four runs, all recorded as no-load starts of ten minutes; no entry addresses the load requirement. No record of any load test of the uninterruptible power supply was produced, and the facilities manager confirmed that none has been performed since the unit was installed. The unit’s batteries carry a manufacturer’s stated service life shorter than the period since installation. Neither foundry was examined for this finding.
RequirementISO/IEC 27001 Annex A.7.11 requires information processing facilities to be protected from power failures and other disruptions caused by failures in supporting utilities. The organisation’s physical security procedure, section 9, sets the testing by which it satisfies itself that its protection works: the uninterruptible power supply load-tested every six months and the standby generator run under load quarterly, with results recorded.
GradeMajor — the organisation determined what testing its own protection requires and has performed none of it to that specification across the whole period, so the protection it relies on is unverified rather than imperfectly verified; the battery age makes the shortfall material rather than administrative.

The second: A.7.13

StatementThe environmental monitoring equipment at head office is not maintained in accordance with the organisation’s maintenance schedule.
Objective evidenceThe organisation’s physical security procedure, section 11, requires the head office environmental monitoring system to be serviced annually by the supplying contractor. The service record shows the last service twenty-two months before the audit, and the contractor’s certificate held on file expired eleven months before the audit. The facilities manager stated that the maintenance contract lapsed at renewal, that a replacement has since been placed with the same contractor, and that the first service under it is scheduled but has not yet fallen due. Service records for the site’s four other items of maintained plant were sampled and are current. The system was observed to be powered and displaying readings consistent with the conditions in the room.
RequirementISO/IEC 27001 Annex A.7.13 requires equipment to be maintained correctly to ensure the availability, integrity and confidentiality of information. The organisation’s physical security procedure, section 11, sets the annual service as the means of doing so for this equipment.
GradeMinor — one item of equipment, at one location, is outside its maintenance schedule; the schedule exists, the site’s other maintained plant is current, and the arrangement has been re-placed with a service scheduled, so what the evidence shows is a lapse in a maintained regime rather than the absence of one.

Note that the two findings are graded differently on evidence gathered the same afternoon. That is not inconsistency. The first says a whole class of protection has never been verified in the way the organisation itself specified; the second says one machine is overdue for a service inside a regime that is otherwise running. Grading both major because they came from the same afternoon, or both minor because they are both about facilities, would be grading by circumstance rather than by evidence.

And notice where the criteria came from in each. Not from a view about how often a generator ought to be tested or a sensor serviced — the standard says nothing about either, and an auditor who supplies a figure has invented a requirement. The criteria are the organisation’s own procedure, which is exactly what makes both findings hard to argue with.

One discipline in writing any of these. Record what you were told as fact where it establishes how far the failure reaches; do not write your own diagnosis of why it happened. Causes are the organisation’s to establish under Clause 10.2, and supplying one hands the auditee something to argue about instead of something to answer. The facilities manager’s account of the lapse and the replacement is recorded because it bears on reach and on grade: it establishes that the gap is one item rather than a regime, and it tells you what to ask next, which is what else that contract covered. Note that it is recorded as what he said, not adopted as the reason the lapse happened.

Want structured preparation?One year of LMS access and HD recordings come with the course.

View the course

Observation in an ISO 27001 audit, and its limits

Physical controls produce the one kind of evidence nobody prepared for you, and that makes observation valuable. It also makes it easy to over-read.

What an observation gives you is a fact at a moment. A network switch sitting on a shelf in an unlocked storeroom is a fact about that switch at that time. It becomes a finding when you can say what requirement it breaches — here A.7.8, equipment sited securely and protected — and show that it is not a moment. An auditor who writes up a single observation as a control failure will be told, fairly, that it was a one-off, and will have nothing to answer with.

So pair every observation with a document or a record. Ask what the siting requirements are and whether that storeroom is inside them; ask when the site was last walked against those requirements and by whom, and read what they wrote. If the last walk recorded no exceptions, you have moved from an anecdote about a switch to something about the checking. If there has never been a walk, you have moved somewhere else again.

Major or minor in ISO 27001 Annex A.7

Major territory: protection the organisation relies on that has never been verified; equipment disposed of with no assurance about what was on it; siting and cabling requirements the organisation set and applied nowhere.

Minor territory: one maintenance visit late in an otherwise maintained schedule; one asset off-premises without the recorded authorisation the procedure asks for; one item sited outside the requirements where the rest of the site meets them.

Escalation: physical failures in several unrelated controls at the same site usually mean nobody owns physical security, which is worth pursuing at A.5.2 or Clause 5.3 rather than as a run of separate minors.

A last word on what this page is not. Fourteen controls is not fourteen inspections. The temptation in a physical audit is to see everything and test nothing, because everything is visible. Choose the controls the organisation’s own risk assessment and Statement of Applicability point you at, and follow each one from its requirement to its record to the thing itself.

ISO 27001 Annex A.7: what does each physical control require?

Pick a control to see what it requires in one line.

How to use it: Choose the option that fits you from the list. The answer appears below.

From the table in this article. A.7.4 Physical security monitoring is the one new control in this theme.

Frequently asked questions about ISO 27001 Annex A.7

How many controls are in ISO 27001 Annex A.7?

Fourteen, covering perimeters, entry, offices and rooms, monitoring, environmental threats, working in secure areas, clear desk and screen, equipment siting, off-premises assets, storage media, supporting utilities, cabling, maintenance and disposal.

Which ISO 27001 Annex A.7 control is new in the 2022 revision?

A.7.4, physical security monitoring, which requires premises to be continuously monitored for unauthorised physical access. It is one of the eleven controls added by the 2022 revision.

Does ISO 27001 Annex A.7 apply to an organisation with no offices?

Several of the controls do, and the argument that none applies rarely survives examination. Equipment exists somewhere, storage media are acquired and disposed of, and assets are off-premises by definition. Any exclusion has to be justified in the Statement of Applicability, and a blanket one is the easiest kind to test.

Can a site walk produce an ISO 27001 nonconformity on its own?

It can produce the evidence for one, but a single observation is a fact at a moment. Pair it with the requirement it breaches and with a document or record that shows the fact is not isolated, before you write it up.

Who is the right person to interview for ISO 27001 Annex A.7?

Facilities, usually, rather than the security manager. The arrangements are theirs, the records are theirs, and the gap between what the information security policy says and what facilities actually does is where the findings are.

The other three ISO 27001 Annex A themes

the A.5 organizational controls

the A.6 people controls

the A.8 technological controls

practice questions on Annex A

For the requirements these controls sit alongside, which record evidences which clause matches each clause to the record that evidences it, and the clause map for lead auditors sets out the whole of Clauses 4 to 10.

3FOLD TRAINING is a CQI and IRCA Approved Training Partner, ATP number 6039853. Its ISO 27001 Lead Auditor training course is the CQI and IRCA Certified ISO/IEC 27001:2022 Lead Auditor (Information Security Management Systems) Training Course. The course identification number is 2889. Both the partner approval and the course certification are on 3FOLD TRAINING’s Approved Training Partner record, and any provider’s certified courses can be looked up in CQI and IRCA’s own directory of certified courses and approved training partners. The course page carries the schedule and what the course includes. If you would rather ask a person first, use the course enquiry form.

Booking a PR373 course? See the schedule, trainers and what’s included.

View the course

CQI and IRCA Approved Training Partner · ATP 6039853 · PR373, Course Approval No. 2889
3FOLD Training · Learn. Certify. Advance.


No comments
0

About 3FOLD

Established in 2008, we specialize in international professional certification and qualification. Mobile: +971.50.4819989

Leave a reply Cancel reply

COURSE ENQUIRY FORM



    Contact us on WhatsApp

    Recent Posts

    • Why Is the ISO 45001 Lead Auditor Course 40 Hours?
    • ISO 45001 Lead Auditor Course Length: How Long?
    • Auditing Incident Management Under ISO 27001
    • Auditing Supplier and Third-Party Security
    • Auditing Backup and Recoverability: ISO 27001

    3FOLD Training

    Your Ultimate Resource for Professional Certification and Qualifications.

    Contact us on WhatsApp

    Head Office

    3FOLD Training FZE
    1003, Park Avenue, Dubai Silicon Oasis, Dubai.
    +971 4 5776146+971 50 4819989
    online@3foldtraining.com

    Branch Office

    • 3FOLD Training
    • Plot No: 1342, HIG, TNHB Main Road, Sithalapakkam, Chennai – 600126.
    • +91 91762 57536

    SUPPORT

    Enquiry
    Contact Us
    Certificate Registry
    Privacy Policy
    Refund and Cancellation Policy
    Terms and Conditions

    © 2026 · 3FOLD Training FZE. All rights reserved

    Prev Next
    Learn. Certify. Advance.

    Advance your career with globally recognized certifications

    • PMI Authorized Training Partner
    • CQI IRCA Approved Training Partner
    • AACEI Approved Education Provider
    30,000+ learners · 100+ countries · 4.9★ from 1,200+ Google reviews

    Get course details and expert guidance

    Ask about fees, syllabus, eligibility and the certification path



      Chat on WhatsApp

      We respect your privacy. No spam. Your details are safe with us.

      WhatsApp
      Hello, welcome to 3FOLD!
      How can we assist you?
      Open chat